DIN rail mounting and panel fit
The S0 frame (85 mm high, 97 mm deep) allows side-by-side mounting with zero spacing, so a multi-contactor bank fits a standard 600 mm wide enclosure backplate without crowding.
Motor switching ratings and thermal limits
AC-3 motor switching is rated up to 690 V, delivering 23 kW at 400 V and 40 kW at 690 V at 60 °C ambient. The 1 000 cycles/hour maximum for AC-3 duty matches typical conveyor or pump cycling; AC-4 (inching/plugging) is capped at 300 cycles/hour to protect the contacts.
Auxiliary contact block ratings
Built-in auxiliary contacts handle 6 A at 24 V, 10 A at 230 V, and 3 A at 400 V AC — enough for a PLC input or a small pilot relay. The 0.25 A at 50 Hz and 0.28 A at 60 Hz figures likely reflect the coil holding current.