Siemens 3RT6024-1AP00 SIRIUS Power Contactor, S0, 23 kW at 4

MPN3RT6024-1AP00

Siemens SIRIUS S0 power contactor, 3RT6024-1AP00, 23 kW at 400 V AC-3e, screw terminals, 45 mm wide, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RT6024-1AP00 — Identification
ParameterValue
Contactor frame sizeS0
3RT6024-1AP00 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT6024-1AP00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz230 V
3RT6024-1AP00 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT6024-1AP00 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 63 A
Short-circuit coordination type 2, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 25 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT6024-1AP00 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
Side-by-side mountingYes
3RT6024-1AP00 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT6024-1AP00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT6024-1AP00 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth97 mm
3RT6024-1AP00 — Specifications
ParameterValue
At AC5 000 1/h

Product details

The Siemens 3RT6024-1AP00 is a SIRIUS S0 power contactor rated for 23 kW at 400 V at 60 °C in AC-3e duty, which means it handles the full load of a 23 kW motor without derating at that ambient temperature. The AC-3e rating is the key figure for motor switching — it governs the contactor's ability to make and break locked-rotor current. For resistive loads (AC-1), the maximum switching rate is 1 000 1/h, while for motor duty (AC-3) it's also 1 000 1/h; the more severe AC-4 duty (plugging/reversing) is limited to 300 1/h. At 45 mm wide, it occupies a single 9 mm pitch unit on the rail — standard for the S0 frame size. Main and auxiliary circuits both use screw-type terminals, accepting 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire. The main contact minimum cross-section is 10 mm² at both 40 °C and 60 °C, so you don't need to upsize the cable for higher ambient. Coil draws 6 A at 24 V rated value, 1 A at 110 V, 0.3 A at 220 V, and 10 A at 230 V — these are inrush figures typical for the S0 coil family.

Substance prohibitance per RoHS/REACH applies from 05/01/2012, so the part is compliant with current EU substance restrictions.

Integration Notes

The 45 mm width per unit means a 4-contactor group fits in 180 mm of rail — useful for compact motor control centers.

Frequently asked questions

What is the 3RT6024-1AP00 rated for in motor duty?

It delivers 23 kW at 400 V at 60 °C in AC-3e duty, with a maximum switching rate of 1 000 operations per hour. The AC-3 rated voltage maximum is 690 V.

Where can I buy the 3RT6024-1AP00 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

Will the 3RT6024-1AP00 fit in a panel designed for the 3RT6025-1AL20?

Both are S0 frame contactors with the same 45 mm width and DIN-rail mounting, so the physical footprint is identical. The difference is in the coil voltage and power rating — verify the coil matches your control voltage and the load current stays within the 3RT6024-1AP00's AC-3e rating.

What compliance documentation does Siemens provide for this contactor?

The part carries RoHS/REACH compliance with a substance prohibitance date of 05/01/2012. The insulation voltage is rated 690 V, and the degree of pollution is 3 per IEC standards.