Skip to main content
Siemens 3RT6025-1AM00 — Contactors

Siemens 3RT6025-1AM00 SIRIUS Power Contactor, S0, 23 kW at 4

MPN3RT6025-1AM00

Siemens SIRIUS, power contactor, type 3RT6025-1AM00, size S0, screw-type terminals, AC-3 rated 690 V, 23 kW at 400 V 60 °C, 45 mm width, snap-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT6025-1AM00 — Identification
ParameterValue
Contactor frame sizeS0
3RT6025-1AM00 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT6025-1AM00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz220 V
3RT6025-1AM00 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT6025-1AM00 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 63 A
Short-circuit coordination type 2, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 25 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT6025-1AM00 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT6025-1AM00 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT6025-1AM00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT6025-1AM00 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth97 mm
3RT6025-1AM00 — Specifications
ParameterValue
At AC5 000 1/h

Product details

The 3RT6025-1AM00: Rated for AC-3 and AC-3e duty up to 690 V, it handles motor loads up to 23 kW at 400 V at 60 °C ambient, and 40 kW at 690 V at 60 °C. The 690 V rating means it can switch motors on 690 V line-to-line systems common in heavy industrial plants, not just the standard 400 V distribution. Mechanical endurance is rated at 10 million operating cycles typical, with electrical endurance at AC-3 and AC-3e maximum 1,000 switching cycles per hour. At AC-4 (plugging/reversing) the maximum drops to 300 cycles per hour — a real constraint if the application involves frequent inching or reversing under load.

Side-by-side mounting is permitted, so multiple contactors can be ganged without spacing gaps, saving rail real estate. Main and auxiliary/control circuits use screw-type terminals. The main circuit accepts 2x (0.5…1.5 mm²) solid/stranded or 2x (0.75…2.5 mm²), with a minimum 10 mm² conductor at both 40 °C and 60 °C. AWG equivalents are 2x (16…12) and 2x (14…8). Strip and torque per the terminal marking — the screw terminals are field-proven, no special tooling required.

Substance prohibitance date of 05/01/2012 confirms RoHS compliance (EU RoHS recast).

MPN