Motor Duty & Thermal Capacity
The 3RT6027-1AL20: Rated motor power at 60 °C: 15.5 kW at 230 V, 27.5 kW at 400 V, 47.5 kW at 690 V. These are the derated figures for continuous operation at elevated panel temperature — the real-world selection point for a panel OEM. Pollution degree 3 suits industrial environments with conductive contamination.
Side-by-side mounting permitted. Accepts 2x (0.5…1.5 mm²) or 2x (0.75…2.5 mm²) solid or stranded wire per terminal.
Switching Frequency & Coil Data
Maximum mechanical switching rate: 5 000 operations per hour at AC; AC-1 max 1 000 1/h, AC-3/AC-3e max 750 1/h, AC-4 max 250 1/h. Typical mechanical life: 10 000 000 operations. Coil consumption at 50 Hz is 0.25 A, at 60 Hz 0.28 A. Rated coil voltages and corresponding currents: 24 V (6 A), 110 V (1 A), 220 V (0.3 A), 230 V (10 A), 400 V (3 A), 690 V (1 A).