Siemens 3RT6926-2PA11 Pneumatic Timer Block, On-Delay 10-180

MPN3RT6926-2PA11

Siemens SIRIUS pneumatic time-relay block, on-delay 10…180 s, 1 NO + 1 NC, for 3RT6 motor contactors size S0, screw terminals, clip-on mounting, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT6926-2PA11 — Identification
ParameterValue
Contactor frame sizeS0
3RT6926-2PA11 — Ratings & Performance
ParameterValue
Rated value @ 500 V2.5 A
Rated value @ 690 V1.5 A
3RT6926-2PA11 — Connection & Mounting
ParameterValue
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, solid or stranded0.5 ... 2.5 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodclip-on
3RT6926-2PA11 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-50 ... +80 °C
3RT6926-2PA11 — Mechanical
ParameterValue
Width45 mm
Height45 mm
Depth60 mm

Product details

The Siemens 3RT6926-2PA11 is a pneumatic time-delay relay block designed specifically for the 3RT6 series of motor contactors in size S0. It provides an adjustable on-delay of 10 to 180 seconds, with one normally-open and one normally-closed delayed switching contact. The block clips directly onto the contactor without tools, saving panel space and wiring time.

The auxiliary contact ratings are voltage-dependent: 4 A at 24 V, 2 A at 48 V, 0.7 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, 4 A at 400 V, 0.15 A at 440 V, 2.5 A at 500 V, and 1.5 A at 690 V (–,). These are the maximum continuous currents the contacts can switch at each voltage level; for a 24 VDC PLC output driving a 4 A load, this block handles it, but at 440 V the same contact is limited to 0.15 A — a significant derating that matters when selecting for higher-voltage control circuits. The auxiliary contacts are rated for AC-12 duty at 10 A, and the short-circuit protection required is a gG 10 A fuse at 1 kA per IEC 60947-5-1.

AWG equivalents are 20–14 for auxiliary contacts.

Frequently asked questions

What is the adjustable delay range of 3RT6926-2PA11?

The on-delay is adjustable from 10 to 180 seconds, with a relative accuracy of 10 %.

Does 3RT6926-2PA11 fit contactors other than 3RT6?

This block is designed for 3RT6 motor contactors size S0. It clips onto the contactor front. For other S0 contactor families, verify mechanical compatibility — the mounting interface may differ.

What compliance documentation is available for 3RT6926-2PA11?

The part is RoHS compliant per the substance prohibition date of May 1, 2012. Standard Siemens declarations of conformity and material declarations are available upon request.

Where can I buy 3RT6926-2PA11 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

MPN
3RT6926-2PA11