Size S00 footprint and panel fit
The 3RT7014-1AF01: Depth is 72 mm and height 57.5 mm, so it fits enclosures with limited back-panel clearance.
AC-3 motor switching and coil power
The three main poles are normally open (3 NO), with no NC main contacts. The DC coil draws 0.8 W closing power and only 0.27 W holding power — the low holding dissipation reduces heat buildup inside the enclosure and lets the control transformer be sized for the inrush rather than the sealed current. Switching frequency is rated at 750 operations per hour maximum for AC-3 duty and 250 per hour for AC-4 — the AC-4 limit reflects the higher electrical wear from plugging or inching duty cycles.
Termination and protection coordination
The contactor carries IP20 protection on both the front face and the terminals — finger-safe against accidental contact but not sealed against moisture or dust ingress.
Lifecycle and supply posture
No stock-holding claim is made — each order is quoted to the buyer's required volume.