It carries three main NO contacts and an AC-operated coil, with screw-type terminals on both the main and auxiliary circuits.
The AC coil pulls 0.73 W to close and holds at 0.41 W, so the control transformer sizing should account for the inrush, not just the sealed power. Maximum switching rate is 800 operations per hour in AC-3 and 250 per hour in AC-4 (plugging / inching duty). If your application needs frequent reversing or jogging, stay under the AC-4 ceiling or the contactor will overheat.
Side-by-side mounting is allowed with no derating penalty — useful when packing multiple contactors in a tight row. Dimensions are 55 mm wide, 112 mm high, 115 mm deep, so it fits standard S2 panel cutouts.