The IP20 front enclosure keeps fingers and tools out of the live terminals inside the panel; the terminal area itself is IP00, so it expects enclosure protection.
Ratings That Matter for the Application
The AC-3 maximum switching rate is 800 operations per hour; AC-4 (plugging/reversing) drops to 250 per hour — the mechanical life is there, but the arc erosion under AC-4 is the limiter. For DC-13 loads at 220 V, it's rated 0.3 A, which covers solenoids and brake coils in that voltage class.
Coil and Control Considerations