Skip to main content
Siemens 3RU1116-0CC1 — Overload Relays

Siemens 3RU1116-0CC1 SIRIUS Thermal Overload Relay, CLASS 10

MPN3RU1116-0CC1

Siemens SIRIUS thermal overload relay, 3RU1116-0CC1, CLASS 10, S00 frame, IP20 front, ATEX certified, cage clamp terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RU1116-0CC1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RU1116-0CC1 — Protection & Trip
ParameterValue
Overload current setting range0.18 ... 0.25 A
Trip classCLASS 10
3RU1116-0CC1 — Electrical (main circuit)
ParameterValue
Poles (main circuit)3
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitCage Clamp terminals
Power loss at rated current (hot)4.8 W
Per pole1.6 W
3RU1116-0CC1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gL/gG: 6 A, quick: 10 A
Switching current at 24 V1 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU1116-0CC1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Auxiliary/control circuit connection typeCage Clamp terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (0.5 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²)
Conductor range (AWG), main contacts2x (24 ... 14)
Conductor range (AWG), auxiliary contacts2x (20 ... 14)
3RU1116-0CC1 — Environmental
ParameterValue
Operating temperature-20 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating100 %
Max. installation altitude2 000 m
Shock resistance8g / 10 ms
3RU1116-0CC1 — Mechanical
ParameterValue
Width45 mm
Height92 mm
Depth78 mm
3RU1116-0CC1 — Specifications
ParameterValue
Type Of ProtectionDMT 98 ATEX G 001

Product details

It is the overload element that pairs with a SIRIUS contactor to form a motor starter — the relay monitors motor current and trips on overload, opening the contactor via its auxiliary contacts.

For motors with longer acceleration times (high-inertia loads), a Class 20 or 30 relay would be needed; this part is sized for normal conveyor, pump, and fan starts. The S00 frame size (45 mm wide, 92 mm high, 78 mm deep) is the smallest SIRIUS overload relay footprint, designed for direct mounting to SIRIUS contactors in the same frame size. Stand-alone installation is also supported per the evidence, with 6 mm clearance required at the side and zero clearance needed upwards, forwards, backwards, or downwards — a tight-panel advantage. Cage clamp terminals on both the main current circuit and auxiliary/control circuit accept 2× (0.5 to 2.5 mm²) solid or 2× (0.5 to 1.5 mm²) finely stranded with ferrule. AWG equivalents are 2× (24 to 14) for main contacts and 2× (20 to 14) for auxiliary contacts. This spring-clamp termination eliminates routine re-torquing in high-vibration environments. Auxiliary contact ratings: 1 A at 24 V, 3 A at 120 V, 2 A at 230 V, 1 A at 400 V — these are the switching capacities for the relay's built-in N/C and N/O contacts that signal the contactor coil or PLC input. The 6 kV rated surge voltage resistance (impulse withstand) means the auxiliary circuit can handle transient spikes common in industrial environments without false tripping or contact welding. Shock resistance is 8g for 10 ms, adequate for most fixed industrial machinery but not for mobile equipment with repeated high-G impacts. ATEX certification (DMT 98 ATEX G 001) permits installation in potentially explosive gas atmospheres — the relay itself is not an ignition source when properly installed and within its ratings. This is a documented compliance path for Zone 1 or Zone 2 applications, not a generic 'suitable for hazardous area' claim.

Compliance Documentation

The part carries a substance prohibitance date of 07/01/2006, aligning with the original EU RoHS directive (2002/95/EC) effective date. Full declarations of conformity for ATEX, CE, and applicable IEC/EN standards are available from Siemens documentation — the evidence confirms the ATEX certificate number DMT 98 ATEX G 001, which is a Notified Body certification, not a self-declaration.

Frequently asked questions

Will the 3RU1116-0CC1 fit a panel specified around the 3RH6131-1BF40?

The 3RU1116-0CC1 is a thermal overload relay (size S00, 45 mm wide), while the 3RH6131-1BF40 is a contactor relay — they serve different functions in the circuit. They share the same SIRIUS S00 frame footprint and can be mechanically coupled, but they are not drop-in substitutes for each other. The overload relay mounts directly to a SIRIUS contactor (e.g., 3RT1016 series) to form a motor starter.

MPN
3RU1116-0CC1