Specifications

3RU1116-0HB0 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
3RU1116-0HB0 — Protection & Trip
ParameterValue
Overload current setting range0.55 ... 0.8 A
Trip classCLASS 10
3RU1116-0HB0 — Electrical (main circuit)
ParameterValue
Poles (main circuit)3
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)4.8 W
Per pole1.6 W
3RU1116-0HB0 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gL/gG: 6 A, quick: 10 A
Switching current at 24 V1 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU1116-0HB0 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
3RU1116-0HB0 — Environmental
ParameterValue
Operating temperature-20 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating100 %
Max. installation altitude2 000 m
Shock resistance8g / 10 ms
3RU1116-0HB0 — Mechanical
ParameterValue
Width45 mm
Height87 mm
Depth78 mm
3RU1116-0HB0 — Specifications
ParameterValue
Type Of ProtectionDMT 98 ATEX G 001

Product details

The 3RU1116-0HB0 is the overload relay sibling to the 3RT1023-1AL20 contactor — same S00 frame, same screw-terminal pattern, same mounting footprint. If your panel was laid out for that contactor, this relay clips on without extra drilling or re-termination. The auxiliary contact ratings (1 A at 24 V, 3 A at 120 V, 2 A at 230 V, 1 A at 400 V —,) match the typical PLC or relay interface in a standard motor starter.

Shock rated at 8g / 10 ms — fine for most industrial panels, not for high-vibration mobile equipment without additional support. Temperature range during operation is -20 to +70 °C; storage and transport handle -55 to +80 °C. Power dissipation is 1.6 W per pole — three poles total 4.8 W, negligible for panel thermal budgeting. Wire sizes: solid 2x (0.5…1.5 mm²) and 2x (0.75…2.5 mm²) for main and auxiliary; AWG equivalents 2x (20…16) and 2x (18…14) plus 2x 12 for main.

Frequently asked questions

Where can I buy 3RU1116-0HB0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest functional second-source for 3RU1116-0HB0?

The 3RT1023-1AL20 contactor shares the same S00 frame and screw-terminal layout, so the 3RU1116-0HB0 clips directly onto it without rewiring. No exact second-source relay exists outside the Siemens SIRIUS family.

What compliance documentation does the 3RU1116-0HB0 carry?

RoHS substance prohibition date 01.07.2006 and ATEX approval DMT 98 ATEX G 001 for explosive atmospheres. IP20 front for finger-safe front face.

MPN
3RU1116-0HB0