It provides Class 10 motor protection, meaning it will trip within 10 seconds at 7.2× the set current — the standard trip class for standard-start induction motors driving pumps, fans, and conveyors where the acceleration time is under about 5 seconds.
Mounts directly onto a contactor (fastening method: contactor mounting) and fits the S00 footprint — 45 mm wide, 87 mm tall, 78 mm deep. Zero clearance required upwards, forwards, backwards, and downwards; only 6 mm needed at the side. Wire range for main contacts accepts 2x (0.5…1.5 mm²) solid or 2x (0.75…2.5 mm²) finely stranded with ferrule; auxiliary contacts take 2x (20…16) AWG.