Skip to main content
Siemens 3RU1116-1HB0-ZW95 — Overload Relays

Siemens 3RU1116-1HB0-ZW95 SIRIUS Thermal Overload Relay, Siz

MPN3RU1116-1HB0-ZW95

Siemens SIRIUS thermal overload relay, size S00, 3 poles, Trip Class 10, screw-type terminals, IP20 front, 78 mm depth, contactor mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RU1116-1HB0-ZW95 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RU1116-1HB0-ZW95 — Protection & Trip
ParameterValue
Overload current setting range5.5 ... 8 A
Trip classCLASS 10
3RU1116-1HB0-ZW95 — Electrical (main circuit)
ParameterValue
Poles (main circuit)3
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)6.6 W
Per pole2.2 W
3RU1116-1HB0-ZW95 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gL/gG: 6 A, quick: 10 A
Switching current at 24 V1 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU1116-1HB0-ZW95 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
3RU1116-1HB0-ZW95 — Environmental
ParameterValue
Operating temperature-20 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating100 %
Max. installation altitude2 000 m
Shock resistance8g / 10 ms
3RU1116-1HB0-ZW95 — Mechanical
ParameterValue
Width45 mm
Height87 mm
Depth78 mm
3RU1116-1HB0-ZW95 — Specifications
ParameterValue
Type Of ProtectionDMT 98 ATEX G 001

Product details

Thermal Overload Relay – SIRIUS Size S00, Class 10

Fastens directly to a contactor via the contactor-mounting method — no DIN rail required, though the 45 mm width and 87 mm height keep it within a standard panel footprint. The mounting position allows rotation up to ±135° on a vertical surface and tilting ±45° forward/backward, giving flexibility for tight enclosure layouts. Clearance requirements: 0 mm upwards, forwards, and backwards; 6 mm at the side; 0 mm downwards. Depth is 78 mm including the relay body.

Shock resistance is 8 g for 10 ms. Surge voltage withstand is 6 kV. The relay carries ATEX approval DMT 98 ATEX G 001, making it suitable for use in potentially explosive gas atmospheres when paired with an appropriate contactor and installed per the system certificate.

Wiring & Termination

Main circuit terminals accept solid conductors: 2×(0.5…1.5 mm²) and 2×(0.75…2.5 mm²), or AWG 2×(20…16) and 2×(18…14) plus 2×12. Auxiliary/control terminals take 2×(0.5…1.5 mm²) and 2×(0.75…2.5 mm²) solid, or AWG 2×(20…16) and 2×(18…14). Finely stranded with core-end processing uses the same cross-sections. Power dissipation per pole is 2.2 W.

Frequently asked questions

What compliance documentation does 3RU1116-1HB0-ZW95 carry?

It carries ATEX approval DMT 98 ATEX G 001 for explosive gas atmospheres, and the substance prohibitance date of 07/01/2006 aligns with RoHS/REACH compliance timelines. IP20 front protection is rated on the front face.

What are the key mounting clearances for 3RU1116-1HB0-ZW95?

Clearances are 0 mm upwards, forwards, and backwards; 6 mm at the side; 0 mm downwards. Depth is 78 mm, width 45 mm, height 87 mm.

Where can I buy 3RU1116-1HB0-ZW95 and get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the Trip Class of 3RU1116-1HB0-ZW95?

Trip Class 10 — it will trip within 10 seconds at 7.2× the current setting, matching standard-start induction motor protection.

MPN
3RU1116-1HB0-ZW95