Skip to main content
Siemens 3RU1126-4AB0-ZW98 — Overload Relays

Siemens 3RU1126-4AB0-ZW98 SIRIUS Thermal Overload Relay, CLA

MPN3RU1126-4AB0-ZW98

Siemens SIRIUS thermal overload relay, 3RU1126-4AB0-ZW98, S0 frame, CLASS 10, 3-pole, screw terminals, IP20 front, ATEX certified.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RU1126-4AB0-ZW98 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S0
Combinable contactor sizesS0
Reference code (IEC 81346-2)F
3RU1126-4AB0-ZW98 — Protection & Trip
ParameterValue
Overload current setting range11 ... 16 A
Trip classCLASS 10
3RU1126-4AB0-ZW98 — Electrical (main circuit)
ParameterValue
Poles (main circuit)3
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)8.1 W
Per pole2.7 W
3RU1126-4AB0-ZW98 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gL/gG: 6 A, quick: 10 A
Switching current at 24 V1 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU1126-4AB0-ZW98 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (16 ... 12), 2x (14 ... 8)
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
3RU1126-4AB0-ZW98 — Environmental
ParameterValue
Operating temperature-20 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating100 %
Max. installation altitude2 000 m
Shock resistance8g / 10 ms
3RU1126-4AB0-ZW98 — Mechanical
ParameterValue
Width45 mm
Height97 mm
Depth96 mm
3RU1126-4AB0-ZW98 — Specifications
ParameterValue
Type Of ProtectionDMT 98 ATEX G 001

Product details

It mounts directly onto a contactor (contactor mounting, per the spec), so the whole motor starter assembly — contactor plus overload — occupies a single DIN-rail footprint in the panel.

The S0 frame gives you a 45 mm wide × 97 mm tall × 96 mm deep package — the standard Siemens S0 footprint, so it drops into any panel already laid out for S0 starters without re-drilling or re-spacing. Screw-type terminals on main and auxiliary circuits: 2× (0.5…1.5 mm²) solid or 2× (0.75…2.5 mm²) stranded for aux contacts, and 2× (16…12) AWG or 2× (14…8) AWG for main power terminals. The relay is designed for a protected enclosure. Rated surge voltage resistance of 6 kV, shock resistance of 8g / 10 ms, and an operating temperature range of -20 to +70 °C with 100 % relative humidity — this is a robust industrial relay that handles the vibration and thermal cycling of a typical machine-tool or conveyor line.

RoHS compliance date of 07/01/2006 is on record, and the IEC 81346-2 reference code is F (protective device).

Frequently asked questions

Will 3RU1126-4AB0-ZW98 drop into a panel that was specified around 3RT6028-1AB00 without rewiring?

The 3RU1126-4AB0-ZW98 is a thermal overload relay (S0 frame), while the 3RT6028-1AB00 is a contactor — they serve different functions in the starter assembly. The 3RU1126 mounts onto a contactor, so it would not directly replace a contactor; you would need the matching contactor (e.g., a 3RT2 series in S0) to pair with it.

MPN
3RU1126-4AB0-ZW98