It is a 3-pole device with screw-type terminals for both main and auxiliary circuits, and carries a Class 10 trip characteristic — meaning it will trip within 10 seconds at 7.2× the set current, matching the thermal time constant of standard induction motors during a locked-rotor event.
Mounts directly onto a contactor via the fastening method (contactor mounting), with a vertical mounting surface that allows ±135° rotation and ±45° tilt front-to-back. The S0 footprint (45 mm wide, 97 mm high, 96 mm deep) fits standard DIN-rail enclosures without crowding adjacent devices.
Wiring and terminal capacity
Main circuit terminals accept 2× (0.5…1.5 mm²) solid or 2× (0.75…2.5 mm²) solid, with AWG equivalents 2× (16…12) and 2× (14…8). Auxiliary/control circuit terminals accept 2× (20…16) and 2× (18…14) AWG. Finely stranded wire with core-end processing is also supported. Power dissipation per pole is 2.7 W.
Auxiliary contact ratings vary by voltage: 1 A at 24 V, 0.22 A at 110 V, 3 A at 120 V, 0.22 A at 125 V, 0.11 A at 220 V, 2 A at 230 V, and 1 A at 400 V. These cover typical control-circuit voltages in both North American and IEC panels.
Shock and compliance
Shock resistance is 8g for 10 ms. Substance prohibitance date is 07/01/2006 (RoHS compliance).