Skip to main content
Siemens 3RU1136-4GD0 — Overload Relays

Siemens 3RU1136-4GD0 SIRIUS Thermal Overload Relay, Size S2,

MPN3RU1136-4GD0

Siemens SIRIUS thermal overload relay, Size S2, Trip Class 10, 3RU1136-4GD0, contactor mounting, IP20 front, ATEX approved.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RU1136-4GD0 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S2
Combinable contactor sizesS2
Reference code (IEC 81346-2)F
3RU1136-4GD0 — Protection & Trip
ParameterValue
Overload current setting range36 ... 45 A
Trip classCLASS 10
3RU1136-4GD0 — Electrical (main circuit)
ParameterValue
Poles (main circuit)3
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)15.6 W
Per pole5.2 W
3RU1136-4GD0 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gL/gG: 6 A, quick: 10 A
Switching current at 24 V1 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU1136-4GD0 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Auxiliary/control circuit connection typeCage Clamp terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (0.5 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²)
Conductor range (AWG), main contacts2x (18 ... 3), 1x (18 ... 1)
Conductor range (AWG), auxiliary contacts2x (20 ... 14)
3RU1136-4GD0 — Environmental
ParameterValue
Operating temperature-20 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating100 %
Max. installation altitude2 000 m
Shock resistance8g / 10 ms
3RU1136-4GD0 — Mechanical
ParameterValue
Width55 mm
Height105 mm
Depth118 mm
3RU1136-4GD0 — Specifications
ParameterValue
Type Of ProtectionDMT 98 ATEX G 001

Product details

The Siemens 3RU1136-4GD0 is a SIRIUS thermal overload relay in Size S2, Trip Class 10, designed to protect motors against overload and phase failure by mounting directly to a contactor. Rated for 5.2 W per pole, it handles the heat from sustained overloads without nuisance tripping in a panel environment. The front panel carries IP20 protection, meaning it's safe from accidental finger contact — standard for enclosed industrial control panels.

Fastens directly to a contactor via the contactor mounting method, eliminating the need for separate DIN-rail clips or brackets. Mounting position allows rotation of ±135° and tilt of ±45° front/back on a vertical surface, giving panel builders flexibility in tight enclosures. Dimensions are 118 mm deep, 55 mm wide, and 105 mm tall, with zero clearance needed upwards, forwards, or backwards — only 6 mm at the side for airflow. Main circuit terminals accept solid 2x (0.5...2.5 mm²) or stranded up to 2x (0.75...25 mm²) and single 0.75...35 mm²; auxiliary and control circuit uses cage clamp terminals for 2x (0.5...1.5 mm²) finely stranded with ferrule.

Duty and Environment

Operates from -20 to +70 °C, stores and ships from -55 to +80 °C, with 100 % relative humidity during operation — suitable for unconditioned plant floors. Surge voltage resistance rated at 6 kV, and shock resistance of 8g for 10 ms, so it holds up in vibrating machinery like conveyors or compressors.

Frequently asked questions

Is 3RU1136-4GD0 available via RFQ confirmation and what is the lead time?

Availability and current pricing are confirmed at quote time. Submit an RFQ for a firm lead time and stock check through our sourcing desk.

What is 3RU1136-4GD0's listed depth?

The depth is 118 mm, with a width of 55 mm and height of 105 mm.

What compliance documentation does 3RU1136-4GD0 carry?

It carries ATEX approval (DMT 98 ATEX G 001) and a substance prohibitance date of 07/01/2006, indicating RoHS compliance.

MPN
3RU1136-4GD0