Specifications

3RU1136-4HB1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S2
Combinable contactor sizesS2
Reference code (IEC 81346-2)F
3RU1136-4HB1 — Protection & Trip
ParameterValue
Overload current setting range40 ... 50 A
Trip classCLASS 10
3RU1136-4HB1 — Electrical (main circuit)
ParameterValue
Poles (main circuit)3
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)15.6 W
Per pole5.2 W
3RU1136-4HB1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gL/gG: 6 A, quick: 10 A
Switching current at 24 V1 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU1136-4HB1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RU1136-4HB1 — Environmental
ParameterValue
Operating temperature-20 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating100 %
Max. installation altitude2 000 m
Shock resistance8g / 10 ms
3RU1136-4HB1 — Mechanical
ParameterValue
Width55 mm
Height105 mm
Depth118 mm
3RU1136-4HB1 — Specifications
ParameterValue
Type Of ProtectionDMT 98 ATEX G 001

Product details

Front IP20, ATEX DMT 98 G 001 certified for explosive atmospheres. Mounting is standalone with flexibility: vertical surface, ±135° rotatable, ±45° tiltable front/back.

The Size S2 frame mates with Siemens S2 contactors (3RT2 series). Standalone installation, not DIN-rail snap-on; plan for panel-mount with the 55×105 mm footprint and 118 mm depth. The 5.2 W per pole heat dissipation adds up to 15.6 W total — account for that in enclosure thermal calculations.

Standalone installation with screw terminals. Wire ranges: main circuit accepts stranded 2×(0.75…25 mm²) or single 0.75…35 mm²; auxiliary contacts take solid 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²), also finely stranded with core-end processing. AWG equivalents for aux: 2×(20…16) and 2×(18…14). Shock rated 8g/10 ms. Storage and transport -55…+80 °C, operating -20…+70 °C, 100 % RH during operation.

Frequently asked questions

Where can I buy 3RU1136-4HB1?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is the depth of 3RU1136-4HB1?

118 mm depth, with 55 mm width and 105 mm height.

What compliance documentation does 3RU1136-4HB1 carry?

ATEX DMT 98 ATEX G 001 for explosive atmospheres, IP20 front protection, substance prohibitance date 07/01/2006 (RoHS/REACH compliance indicator). Reference code per IEC 81346-2: F.

Will 3RU1136-4HB1 drop into a panel specified for 3RU2116-1FC1?

Both are SIRIUS Size S2 overload relays with the same mounting footprint and screw terminals. The 3RU1136-4HB1 is a direct functional match for the same contactor frame — no rewiring needed if the panel was laid out for a Size S2 relay.

MPN
3RU1136-4HB1