Skip to main content
Siemens 3RU1146-4MB0-ZW97 — Overload Relays

3RU1146-4MB0-ZW97 - Siemens

MPN3RU1146-4MB0-ZW97

Overload relay 80...100 A For motor protection Size S3, Class 10 Contactor mounting Main circuit: Screw terminal Auxiliary circuit: Screw terminal Manual-Automatic-Reset Reusable packaging Pack = 25 units!!! Phased-out product!!! Successor is SIRIUS 3RU2

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RU1146-4MB0-ZW97 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S3
Combinable contactor sizesS3
Reference code (IEC 81346-2)F
3RU1146-4MB0-ZW97 — Protection & Trip
ParameterValue
Overload current setting range80 ... 100 A
Trip classCLASS 10
3RU1146-4MB0-ZW97 — Electrical (main circuit)
ParameterValue
Poles (main circuit)3
Rated insulation voltage (AC, pollution degree 3)1 000 V
Rated surge withstand voltage8 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)21 W
Per pole7 W
3RU1146-4MB0-ZW97 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gL/gG: 6 A, quick: 10 A
Switching current at 24 V1 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU1146-4MB0-ZW97 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (10 ... 1/0), 1x (10 ... 2/0)
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
3RU1146-4MB0-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating100 %
Max. installation altitude2 000 m
Shock resistance8g / 10 ms
3RU1146-4MB0-ZW97 — Mechanical
ParameterValue
Width70 mm
Height120 mm
Depth140 mm
3RU1146-4MB0-ZW97 — Specifications
ParameterValue
Type Of ProtectionDMT 98 ATEX G 001
MPN
3RU1146-4MB0-ZW97