Skip to main content
Siemens 3RU2116-0GC0-ZX95 — Overload Relays

Siemens 3RU2116-0GC0-ZX95 SIRIUS Thermal Overload Relay, Siz

MPN3RU2116-0GC0-ZX95
Active

Siemens SIRIUS, thermal overload relay, Size S00, Trip Class 10, 690 V rated insulation, spring-loaded terminals, contactor mounting, 87 x 45 x 70 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RU2116-0GC0-ZX95 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RU2116-0GC0-ZX95 — Protection & Trip
ParameterValue
Overload current setting range0.45 ... 0.63 A
Trip classCLASS 10
Overload release typethermal
3RU2116-0GC0-ZX95 — Electrical (main circuit)
ParameterValue
Rated operational current0.63 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitspring-loaded terminals
Power loss at rated current (hot)4.8 W
Per pole1.6 W
3RU2116-0GC0-ZX95 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU2116-0GC0-ZX95 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typespring-loaded terminals
Removable aux./control terminalNo
Conductor cross-section: solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts1x (20 ... 12)
Conductor range (AWG), auxiliary contacts2x (20 ... 14)
3RU2116-0GC0-ZX95 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
3RU2116-0GC0-ZX95 — Mechanical
ParameterValue
Width45 mm
Height87 mm
Depth70 mm

Product details

The 3RU2116-0GC0-ZX95 is a Siemens SIRIUS thermal overload relay in the Size S00 frame, designed to protect AC motor circuits against overload and phase-loss conditions. The relay is rated for a maximum insulation voltage of 690 V (AC-3e rated value maximum 690 V) and carries auxiliary contact ratings across multiple control voltages: 2 A at 24 V, 3 A at 120 V, 2 A at 230 V, 1 A at 400 V, and others covering 60 V through 690 V. These are the contacts that signal the trip condition — the unit's note indicates it is configured for message Tripped.

This relay snaps onto a compatible contactor (Size S00 footprint), occupying no extra DIN-rail width — the 45 mm width and 87 mm height keep the assembly compact. Connections are spring-loaded terminals accepting 2 × (0.5... 2.5 mm²) solid or stranded conductors; no screwdriver needed for the main circuit, though the auxiliary screw terminals require a 3 mm diameter blade (3.0 × 0.5 mm tip).

Frequently asked questions

What is 3RU2116-0GC0-ZX95's listed note (for message Tripped) on this component line?

The note indicates the relay is configured for message Tripped — meaning the auxiliary contacts signal a trip condition rather than a normal state.

What is 3RU2116-0GC0-ZX95's listed depth (70 mm) on this component line?

The depth is 70 mm, which is the dimension from the contactor face to the rear of the relay when mounted.

Will 3RU2116-0GC0-ZX95 drop into a panel that was specified around 3RH6131-1AP00 without rewiring?

No — the 3RU2116-0GC0-ZX95 is a thermal overload relay that mounts on a contactor, while the 3RH6131-1AP00 is a contactor/auxiliary contact block. They serve different functions and are not drop-in replacements.

MPN
3RU2116-0GC0-ZX95