Skip to main content
Siemens 3RU2116-1BB0 — Overload Relays

Siemens 3RU2116-1BB0 SIRIUS Thermal Overload Relay, S00, Cla

MPN3RU2116-1BB0
Active

Siemens SIRIUS 3RU2116-1BB0 thermal overload relay, size S00, Class 10, 690 V rated, contactor-mount, screw terminals.

$27.94Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RU2116-1BB0 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RU2116-1BB0 — Protection & Trip
ParameterValue
Overload current setting range1.4 ... 2 A
Trip classCLASS 10
Overload release typethermal
3RU2116-1BB0 — Electrical (main circuit)
ParameterValue
Rated operational current2 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)5.7 W
Per pole1.9 W
3RU2116-1BB0 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU2116-1BB0 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
3RU2116-1BB0 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
3RU2116-1BB0 — Mechanical
ParameterValue
Width45 mm
Height76 mm
Depth70 mm

Product details

Siemens SIRIUS 3RU2116-1BB0 is a thermal overload relay in the S00 frame size, Class 10 trip. It mounts directly to a contactor and protects AC motors against overload and phase failure. The relay mounts directly onto the contactor via the contactor mounting fastening method, eliminating separate DIN-rail space and wiring between the contactor and overload. Screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire — a standard range for motor feeders up to the S00 frame rating.

The auxiliary contact (integrated design) switches 2 A at 24 V, 3 A at 120 V, 2 A at 230 V, 1 A at 400 V, and 0.75 A at 690 V — these are the make/break capacities for the trip-indication circuit, not the main motor current. The note 'for message Tripped' confirms the auxiliary contact signals the tripped state, so it is wired into the PLC or alarm circuit, not the motor power path. The relay is temperature-compensated from -40 to +60 °C, meaning the trip curve stays within tolerance across that ambient range — important for panels near ovens, outdoors, or in unheated enclosures. Mounting position is any, so the relay can be installed horizontally or vertically without derating.

Substance prohibition date of 10/01/2009 indicates RoHS compliance per the EU directive.

Integration note

Mounts directly to a Siemens contactor of matching S00 frame size — no separate DIN-rail clip needed. The auxiliary contact is integrated, so no add-on block is required for the tripped signal. Screw terminals accept Pozidriv PZ2 screwdriver tip (shaft diameter 5 to 6 mm).

Frequently asked questions

Does the 3RU2116-1BB0 require a separate DIN-rail mount?

No. It uses contactor mounting — it fastens directly onto a Siemens S00 contactor, saving DIN-rail space and reducing wiring between the contactor and overload relay.

MPN
3RU2116-1BB0