Skip to main content
Siemens 3RU2116-1DC1 — Overload Relays

3RU2116-1DC1 - Siemens

MPN3RU2116-1DC1
Active

Overload relay 2.2...3.2 A Thermal For motor protection Size S00, Class 10 Stand-alone installation Main circuit: Spring-type terminal Auxiliary circuit: spring-type terminal Manual-Automatic-Reset

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RU2116-1DC1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RU2116-1DC1 — Protection & Trip
ParameterValue
Overload current setting range2.2 ... 3.2 A
Trip classCLASS 10
Overload release typethermal
3RU2116-1DC1 — Electrical (main circuit)
ParameterValue
Rated operational current3.2 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitspring-loaded terminals
Power loss at rated current (hot)5.7 W
Per pole1.9 W
3RU2116-1DC1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU2116-1DC1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typespring-loaded terminals
Removable aux./control terminalNo
Conductor cross-section: solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts1x (20 ... 12)
Conductor range (AWG), auxiliary contacts2x (20 ... 14)
3RU2116-1DC1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
3RU2116-1DC1 — Mechanical
ParameterValue
Width45 mm
Height102 mm
Depth79 mm
MPN