Class 10 trip and motor protection
The 3RU2116-1EC0-ZW97 is a SIRIUS S00 thermal overload relay from Siemens, designed for motor protection in control panels.
Mounts directly onto the contactor via the fastening method — no DIN rail needed, which saves panel space. Any mounting position is allowed, so it can be oriented to suit the enclosure layout. A 3.0 x 0.5 mm screwdriver tip is specified for the terminal screws — standard for this class of relay.
Auxiliary contact and status signalling
An integrated auxiliary switch provides a 'Tripped' message contact, giving a clear status signal back to the PLC or HMI. The contact ratings cover control voltages from 24 V (2 A) up to 400 V (1 A), with specific ratings at 120 V (3 A) and 230 V (2 A) — typical for North American and European control circuits. The thermal overload release is temperature-compensated from -40 to +60 °C, so the trip curve stays accurate across a wide ambient range — important for outdoor or unconditioned enclosures.
The MTTF at high demand rate is 2,280 years, reflecting the electromechanical reliability of the design.