Skip to main content
Siemens 3RU2116-1JC1 — Overload Relays

Siemens 3RU2116-1JC1 thermal overload relay, S00, CLASS 10,

MPN3RU2116-1JC1
Active

Siemens SIRIUS 3RU2116-1JC1, size S00 thermal overload relay, CLASS 10, 690 V rated, spring-loaded terminals.

$101.92Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RU2116-1JC1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RU2116-1JC1 — Protection & Trip
ParameterValue
Overload current setting range7 ... 10 A
Trip classCLASS 10
Overload release typethermal
3RU2116-1JC1 — Electrical (main circuit)
ParameterValue
Rated operational current10 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitspring-loaded terminals
Power loss at rated current (hot)6.6 W
Per pole2.2 W
3RU2116-1JC1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU2116-1JC1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typespring-loaded terminals
Removable aux./control terminalNo
Conductor cross-section: solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts1x (20 ... 12)
Conductor range (AWG), auxiliary contacts2x (20 ... 14)
3RU2116-1JC1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
3RU2116-1JC1 — Mechanical
ParameterValue
Width45 mm
Height102 mm
Depth79 mm

Product details

The 3RU2116-1JC1: Mounts in any position, stand-alone installation. Spring-loaded terminals on the main circuit accept 2× (0.5 to 2.5 mm²) solid or stranded wire — no screw torque to verify, just strip and push. The auxiliary switch is integrated, saving a separate contact block. Temperature compensation is active from -40 to +60 °C, so the trip curve stays accurate across a wide ambient range. Dimensions: 45 mm wide, 102 mm high, 79 mm deep — fits standard 45 mm DIN-rail spacing.

Frequently asked questions

What is the note 'for message Tripped' on this relay?

The relay carries a note 'for message Tripped' — this is a diagnostic output that signals when the relay has tripped due to overload, typically used to trigger an alarm or PLC input.

What are the key dimensions of the 3RU2116-1JC1?

Width: 45 mm, height: 102 mm, depth: 79 mm. It fits standard DIN-rail mounting and is size S00.

Does the 3RU2116-1JC1 have temperature compensation?

Yes, it is temperature-compensated from -40 to +60 °C, so the trip characteristic remains accurate across a wide ambient range.

What compliance documentation is available for the 3RU2116-1JC1?

The relay has a substance prohibitance date of 10/01/2009, indicating RoHS compliance. For full documentation (UL, IEC, REACH), the manufacturer provides declarations on request.

MPN