Siemens 3RU2116-1KB1 SIRIUS Overload Relay, Class 10

MPN3RU2116-1KB1
Active

Siemens SIRIUS 3RU2116-1KB1 thermal overload relay, Size S00, Trip Class 10, 5.5 kW at 400 V, screw terminals, stand-alone installation.

$34.29Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RU2116-1KB1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F

Protection & Trip

3RU2116-1KB1 — Protection & Trip
ParameterValue
Overload current setting range9 ... 12.5 A
Trip classCLASS 10
Overload release typethermal

Electrical (main circuit)

3RU2116-1KB1 — Electrical (main circuit)
ParameterValue
Rated operational current12.5 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)6.6 W
Per pole2.2 W

Auxiliary contacts

3RU2116-1KB1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A

Connection & Mounting

3RU2116-1KB1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)

Environmental

3RU2116-1KB1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m

Mechanical

3RU2116-1KB1 — Mechanical
ParameterValue
Width45 mm
Height89 mm
Depth80 mm

Product details

Class 10 trip and motor protection

That's the standard for standard-start squirrel-cage motors — it lets the inrush pass during acceleration but catches a stalled rotor before the winding insulation degrades. The 3RU2116-1KB1 is a Size S00 thermal overload relay, the compact frame in the SIRIUS family. It mounts directly below an S00 contactor or stand-alone on the panel via screw terminals. The auxiliary contact set includes a normally closed (NC) and normally open (NO) pair, with the NC contact wired in series with the contactor coil for fail-safe drop-out.

Auxiliary contact ratings and signal wiring

At 230 V it's rated 2 A, and at 400 V it's 1 A. The note 'for message Tripped' means the NC contact opens when the relay trips, giving a hardwired status signal to the controller. The M3 main contact screws are standard for this frame size.

Temperature range and mounting flexibility

Operating temperature spans -40 to +70 °C, with temperature compensation active from -40 to +60 °C. That means the trip characteristic stays accurate even in an unheated enclosure or near a hot motor — the bimetallic strip's ambient drift is corrected electronically. Dimensions are 89 mm high, 45 mm wide, 80 mm deep — the S00 footprint leaves room for terminal blocks alongside in a shallow panel.

MPN
3RU2116-1KB1