Skip to main content
Siemens 3RU2116-1KC1 — Overload Relays

Siemens 3RU2116-1KC1 SIRIUS Thermal Overload Relay

MPN3RU2116-1KC1
Active

Siemens SIRIUS 3RU2116-1KC1 thermal overload relay, size S00, 5.5 kW at 400 V AC-3e, Class 10, 690 V rated insulation, spring-loaded terminals, 45 x 102 x 79 mm.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RU2116-1KC1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F

Protection & Trip

3RU2116-1KC1 — Protection & Trip
ParameterValue
Overload current setting range9 ... 12.5 A
Trip classCLASS 10
Overload release typethermal

Electrical (main circuit)

3RU2116-1KC1 — Electrical (main circuit)
ParameterValue
Rated operational current12.5 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitspring-loaded terminals
Power loss at rated current (hot)6.6 W
Per pole2.2 W

Auxiliary contacts

3RU2116-1KC1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A

Connection & Mounting

3RU2116-1KC1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typespring-loaded terminals
Removable aux./control terminalNo
Conductor cross-section: solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts1x (20 ... 12)
Conductor range (AWG), auxiliary contacts2x (20 ... 14)

Environmental

3RU2116-1KC1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m

Mechanical

3RU2116-1KC1 — Mechanical
ParameterValue
Width45 mm
Height102 mm
Depth79 mm

Product details

S00 frame with spring-clamp wiring

The 3RU2116-1KC1: This is a size S00 thermal overload relay from the SIRIUS family — the smallest frame in the range, at 45 mm wide, 102 mm tall, and 79 mm deep. It mounts in any position and is designed for stand-alone installation, not ganged to a contactor. No screw torque to check — push the ferrule in and the cage holds.

Class 10 trip and motor power ratings

That matches standard motor start profiles for pumps, fans, and compressors where the start time stays under 10 seconds. Current ratings at 480 V and 600 V are both 12.5 A — useful for North American 480 V panels where the motor FLA falls in that range.

Auxiliary contact switching capacity

At 60 V DC it switches 0.3 A, dropping to 0.22 A at 110–125 V DC and 0.11 A at 220 V DC. These are the contact ratings for the trip-signal circuit — the relay's own thermal element handles the motor current. Each pole dissipates 2.2 W at rated current — budget that into the enclosure thermal calculation if multiple relays are stacked.

The MTTF at high demand rate is 2,280 years, which reflects a robust electromechanical design for continuous industrial duty. Storage and transport limits are -55 to +80 °C. The relay carries a substance prohibition date of 10/01/2009, aligning with RoHS and REACH compliance requirements.

Frequently asked questions

What does the 'Note for message Tripped' mean on this relay?

The note indicates that the auxiliary contact position signals the tripped state. When the thermal element operates, the integrated auxiliary switch changes state to indicate an overload condition to the PLC or control system.

What compliance documentation does the 3RU2116-1KC1 carry?

The relay has a substance prohibition date of 10/01/2009, indicating RoHS and REACH compliance. The rated insulation voltage of 690 V and AC-3e switching ratings suggest IEC 60947-4-1 design.

MPN
3RU2116-1KC1