Skip to main content
Siemens 3RU2116-1KJ0 — Overload Relays

Siemens 3RU2116-1KJ0 SIRIUS Thermal Overload Relay, S00, Cla

MPN3RU2116-1KJ0

Siemens SIRIUS 3RU2116-1KJ0 thermal overload relay, size S00, Class 10 trip, 690 V rated, contactor-mounted, integrated auxiliary switch.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RU2116-1KJ0 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RU2116-1KJ0 — Protection & Trip
ParameterValue
Overload current setting range9 ... 12.5 A
Trip classCLASS 10
Overload release typethermal
3RU2116-1KJ0 — Electrical (main circuit)
ParameterValue
Rated operational current12.5 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitRing cable lug connection
Power loss at rated current (hot)6.6 W
Per pole2.2 W
3RU2116-1KJ0 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A
3RU2116-1KJ0 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typering terminal lug connection
Removable aux./control terminalNo
3RU2116-1KJ0 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
3RU2116-1KJ0 — Mechanical
ParameterValue
Width45 mm
Height76 mm
Depth70 mm

Product details

That covers 400 V, 480 V, 600 V, and 690 V line supplies common in European and North American industrial panels. The motor power assignments at those voltages are 5.5 kW at 400 V, 7.5 kW at 500 V, and 7.5 kW at 690 V — so it's sized for a 5.5–7.5 kW motor range depending on your line voltage. The integrated auxiliary switch (1 N/O + 1 N/C) is rated for switching at various control voltages: 2 A at 24 V and 230 V, 3 A at 120 V, 1 A at 400 V, and 0.75 A at 690 V. These are the contact ratings for the trip-indication circuit — the "Tripped" message contact that signals the PLC or annunciator when the relay has operated. At 24 VDC control common in modern panels, you get 2 A switching capacity, enough for a typical PLC input or contactor coil. Power dissipation per pole is 2.2 W, so three poles total 6.6 W under load. That's modest — no special ventilation required in a standard IP20 enclosure, but worth noting if you're packing multiple relays in a small cabinet.

Fastening method is contactor mounting — it snaps directly onto the matching S00 contactor (e.g., 3RT1016 series). No DIN rail required for the relay itself; it rides on the contactor. Dimensions: 45 mm wide, 76 mm high, 70 mm deep — the width matches a standard S00 contactor footprint, so it doesn't add lateral space. Main circuit connection is via ring cable lug (M3 screw), suitable for the current range of an S00 relay. The auxiliary circuit uses screw terminals with a Pozidriv PZ2 tip, 5–6 mm shaft diameter. Temperature compensation is active from -40 °C to +60 °C, so the trip curve stays accurate across the operating range without manual adjustment.

The relay carries a substance prohibition date of 10/01/2009, indicating RoHS compliance from that date forward. MTTF at high demand rate is 2,280 years — a reliability figure that supports safety-related applications where the relay is part of a monitored circuit.

Frequently asked questions

How do I get current pricing and availability for 3RU2116-1KJ0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — we source through independent distribution and quote firm on each request.

Will 3RU2116-1KJ0 drop into a panel that was specified around 3RU2116-1FC1 without rewiring?

Both are S00 frame thermal overload relays with the same mounting footprint and connection method (contactor-mounted, ring cable lug for main circuit). The 3RU2116-1FC1 has a different current setting range; verify your motor FLA falls within the 3RU2116-1KJ0's adjustment range before substituting. Mechanically it's a direct swap.

What compliance documentation does this brand provide for 3RU2116-1KJ0 (RoHS, REACH, UL, IEC)?

The relay carries a substance prohibition date of 10/01/2009, indicating RoHS compliance from that date. The product brand is Siemens SIRIUS, which typically provides CE, UL, CSA, and IEC 60947 certifications for this series. Specific documentation is available upon request with your RFQ.

MPN
3RU2116-1KJ0