Skip to main content
Siemens 3RU2126-4CB1 — Overload Relays

Siemens 3RU2126-4CB1 SIRIUS Overload Relay, CLASS 10, S0

MPN3RU2126-4CB1
Active

Siemens SIRIUS 3RU2126-4CB1 thermal overload relay, CLASS 10 trip class, Size S0, 690 V rated insulation voltage, screw-type terminals, stand-alone mounting.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RU2126-4CB1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S0
Combinable contactor sizesS0
Reference code (IEC 81346-2)F

Protection & Trip

3RU2126-4CB1 — Protection & Trip
ParameterValue
Overload current setting range17 ... 22 A
Trip classCLASS 10
Overload release typethermal

Electrical (main circuit)

3RU2126-4CB1 — Electrical (main circuit)
ParameterValue
Rated operational current22 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)8.1 W
Per pole2.7 W

Auxiliary contacts

3RU2126-4CB1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A

Connection & Mounting

3RU2126-4CB1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalNo
Conductor cross-section: solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (16 ... 12), 2x (14 ... 8)
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)

Environmental

3RU2126-4CB1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m

Mechanical

3RU2126-4CB1 — Mechanical
ParameterValue
Width45 mm
Height97 mm
Depth95 mm

Product details

Trip class and motor protection timing

The 3RU2126-4CB1: If your motor has a long acceleration time (high-inertia fan or crusher), CLASS 10 may nuisance-trip on start; you'd need a CLASS 20 or 30 relay instead. The S0 frame size (97 mm high, 45 mm wide, 95 mm deep) fits the standard SIRIUS contactor footprint — it mounts directly below a 3RT2 contactor of the same size class without extra bracketing.

Auxiliary contact ratings across control voltages

These are the make/break capacities for the signal circuit — the 120 V rating is the highest current point, so if your PLC input module runs on 24 VDC, budget 2 A max per contact. At 60 V and 125 V the contact is rated 0.3 A and 0.22 A respectively — these lower values reflect DC switching limits where arc extinction is harder. For DC control circuits, verify the voltage matches the rating table.

Temperature compensation and mounting flexibility

Temperature compensation is active from -40 °C to +60 °C ambient — the bimetal element adjusts for ambient heat so the trip point stays accurate whether the panel is in a heated factory or an unheated warehouse. Operating range extends to -40 to +70 °C, but above 60 °C the compensation curve stops tracking.

The 3RU2126-4CB1 is the standard SIRIUS thermal overload relay in the S0 frame, not a phase-out or NRND variant. Substance prohibitance date of 10/01/2009 indicates RoHS compliance per Siemens' declaration. The relay carries the SIRIUS brand designation and is designed for the main current circuit with screw-type terminals.

Frequently asked questions

Where can I buy 3RU2126-4CB1 and get a price?

Sourced through independent distribution — quoted to order against your BOM quantity.

What does the 'for message Tripped' note mean on this relay?

The note indicates the auxiliary contact position after a trip event — the N/C contact opens and the N/O contact closes, signaling a 'Tripped' status to the PLC or indicator. It is the standard alarm contact configuration for thermal overload relays.

What compliance documentation does Siemens provide for 3RU2126-4CB1?

RoHS compliance is confirmed by the substance prohibitance date of 10/01/2009. The relay is designed to IEC/EN 60947-4-1 standards for thermal overload relays. Full declarations are available from Siemens upon request.

MPN
3RU2126-4CB1