CLASS 10 trip and motor protection coordination
The 3RU2136-4DB0: This coordinates with standard motor starting profiles — a motor that stalls or jams will be disconnected before the winding insulation reaches its thermal limit. Rated motor power at 400 V is 11 kW, at 500 V is 15 kW, and at 690 V is 22 kW. The continuous current rating at 480 V and 600 V is 25 A. These figures define the maximum motor frame size this relay protects in a given line voltage.
Auxiliary contact signal ratings
These ratings cover direct connection to 24 VDC PLC inputs as well as 120 V and 230 V AC control circuits — no interposing relay needed for most panels.
Fastening method is contactor mounting — this relay snaps directly onto the matching SIRIUS contactor, not onto a DIN rail standalone. Dimensions are 105 mm depth, 55 mm width, 90 mm height. Temperature compensation is active from -40 to +60 °C, ensuring the trip curve stays accurate across the panel's ambient range.