Skip to main content
Siemens 3RU2146-4JD1 — Overload Relays

Siemens 3RU2146-4JD1 SIRIUS Overload Relay, Class 10, S3

MPN3RU2146-4JD1
Active

Siemens SIRIUS 3RU2146-4JD1 thermal overload relay, Class 10, S3 frame size, 70 x 120 x 140 mm, screw-type terminals, 30 kW at 400 V.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RU2146-4JD1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationthermal overload relay
Frame size (overload relay)S3
Combinable contactor sizesS3
Reference code (IEC 81346-2)F

Protection & Trip

3RU2146-4JD1 — Protection & Trip
ParameterValue
Overload current setting range45 ... 63 A
Trip classCLASS 10
Overload release typethermal

Electrical (main circuit)

3RU2146-4JD1 — Electrical (main circuit)
ParameterValue
Rated operational current63 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)1 000 V
Rated value (AC-3e), max.1 000 V
Rated surge withstand voltage8 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)17.1 W
Per pole5.7 W

Auxiliary contacts

3RU2146-4JD1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A, quick: 10 A
Switching current at 24 V2 A
Switching current at 60 V0.3 A
Switching current at 110 V0.22 A
Switching current at 120 V3 A
Switching current at 125 V0.22 A
Switching current at 220 V0.11 A
Switching current at 230 V2 A
Switching current at 400 V1 A

Connection & Mounting

3RU2146-4JD1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typespring-loaded terminals
Removable aux./control terminalNo
Conductor cross-section: solid2x (2.5 ... 16 mm²)
Conductor cross-section: solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²)

Environmental

3RU2146-4JD1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Storage temperature-55 ... +80 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m

Mechanical

3RU2146-4JD1 — Mechanical
ParameterValue
Width70 mm
Height120 mm
Depth140 mm

Product details

S3 frame, Class 10 trip — what that means for your motor circuit

The 3RU2146-4JD1 is a SIRIUS thermal overload relay in the S3 frame size — the physical envelope that tells you which contactor it mates with and how much panel space it needs (70 mm wide, 120 mm high, 140 mm deep).

Motor power match at common line voltages

At 480 V the relay carries 52 A; at 600 V it carries 62 A — useful for North American 480/600 V installations where the motor FLA falls in that range.

Auxiliary contact ratings for PLC and control circuits

The auxiliary contact handles 2 A at 24 V and 2 A at 230 V — the two voltages most common for PLC input modules and control relays. At 120 V it's rated 3 A, which covers most North American control transformer circuits without a contact rating derate. Higher-voltage ratings drop off: 1 A at 400 V, 0.75 A at 690 V — fine for signal feedback to a VFD or remote I/O, but not for power switching.

Environmental range and temperature compensation

Temperature compensation is active from -40 to +60 °C, meaning the trip curve stays accurate without manual adjustment across that band — relevant for enclosures near steam lines or chillers.

Lifecycle and sourcing — active production, quoted to order

Substance prohibitance date of 03/01/2017 confirms RoHS/REACH compliance documentation exists — relevant for EU and pharmaceutical validation dossiers.

Frequently asked questions

How do I get current pricing and availability for 3RU2146-4JD1?

Submit an RFQ for a firm quote.

What does the note 'Tripped' mean on this overload relay?

The note 'Tripped' is a diagnostic signal — it tells the PLC or HMI that the overload relay has operated, not the trip current setting. It's a status message, not a specification value.

What compliance documentation does Siemens provide for 3RU2146-4JD1?

The substance prohibitance date of 03/01/2017 confirms RoHS/REACH compliance documentation exists. UL and IEC certifications are standard for the SIRIUS family, though specific listing numbers are not in this record.

MPN
3RU2146-4JD1