Adjustable current range is 9 to 12.5 A, Trip Class 10.
Rated operational current is 12.5 A at 690 V, 50/60 Hz. Adjustable overload release covers 9 to 12.5 A. Each pole dissipates 2.5 W, total typical power loss 9 W.
Fastening method is contactor mounting — the relay clips directly onto the contactor's output terminals. Mounting position allows a vertical mounting surface with ±135° rotation and ±45° tilt front-to-back, so you have flexibility in panel layout. Required spacing to grounded parts at the side is 6 mm — keep that gap for heat dissipation and creepage. Main circuit screw terminals accept 2× (0.5 to 1.5 mm²) solid/stranded or 2× (0.75 to 2.5 mm²), with tightening torque 3 to 5 N·m. Auxiliary circuit screw terminals take 2× (20 to 16 AWG). Ambient operating temperature is -20 to +70 °C, storage/transport -55 to +80 °C.