Skip to main content
Siemens 3RU6116-0BB1 — Overload Relays

Siemens 3RU6116-0BB1 SIRIUS Overload Relay, 0.14-0.20 A, Cla

MPN3RU6116-0BB1

Siemens SIRIUS thermal overload relay, 3RU6116-0BB1, size S00, adjustable 0.14-0.20 A, Trip Class 10, screw terminals, 690 V rated, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RU6116-0BB1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationThermal overload relay
Combinable contactor sizesS00
3RU6116-0BB1 — Protection & Trip
ParameterValue
Overload current setting range0.14 ... 0.2 A
Trip classCLASS 10
Overload release typethermal
3RU6116-0BB1 — Electrical (main circuit)
ParameterValue
Rated operational current0.2 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)4.8 W
Per pole1.6 W
3RU6116-0BB1 — Auxiliary contacts
ParameterValue
Switching current at 24 V2 A
Switching current at 110 V0.22 A
Switching current at 230 V2 A
3RU6116-0BB1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Conductor cross-section: solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RU6116-0BB1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating0 ... 90 %
Max. installation altitude2 000 m
3RU6116-0BB1 — Mechanical
ParameterValue
Width45 mm
Height89 mm
Depth80 mm

Product details

Its adjustable current response value of 0.14 to 0.20 A means it protects small motors — think coolant pumps, small fans, or conveyor drives — where a standard 0.4 A relay would be too coarse to catch an overload before the winding gets hot. Rated for 690 V operating voltage and fits the S00 contactor frame size, so it mates directly with the matching SIRIUS contactor range without extra bus bars or adapters.

RoHS compliance date of May 1, 2012 is on record, which covers the EU directive. No UL or CSA marks are listed in the spec record, so if your panel requires those, verify the specific variant before committing the BOM line.

Mounts in any position — upright, sideways, upside-down — which helps when you're cramming gear into a tight enclosure. Stand-alone installation, not DIN-rail snap-on; it bolts directly to the panel or to the contactor. The 80 mm depth and 45 mm width mean it fits the standard S00 footprint. Operates from -40 to +70 °C ambient, so it's happy in an unheated pump house or next to a hot motor. 0 to 90% relative humidity during operation — no special derating for damp environments. Shock-rated to 8g / 11 ms per IEC 60068-2-27, which covers most industrial vibration without needing a separate shock mount.

Frequently asked questions

What is the adjustable current range on this overload relay?

The adjustable current response value is 0.14 to 0.20 A, which covers small fractional-horsepower motors.

MPN
3RU6116-0BB1