Siemens 3RU6116-0EB1 SIRIUS Overload Relay, 0.28-0.40 A

MPN3RU6116-0EB1

Siemens SIRIUS 3RU6116-0EB1 thermal overload relay, size S00, 0.28-0.40 A adjustable, Class 10 trip, 690 V, 3-pole, screw terminals, stand-alone installation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RU6116-0EB1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationThermal overload relay
Combinable contactor sizesS00
3RU6116-0EB1 — Protection & Trip
ParameterValue
Overload current setting range0.28 ... 0.4 A
Trip classCLASS 10
Overload release typethermal
3RU6116-0EB1 — Electrical (main circuit)
ParameterValue
Rated operational current0.4 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)4.8 W
Per pole1.6 W
3RU6116-0EB1 — Auxiliary contacts
ParameterValue
Switching current at 24 V2 A
Switching current at 110 V0.22 A
Switching current at 230 V2 A
3RU6116-0EB1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Conductor cross-section: solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RU6116-0EB1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating0 ... 90 %
Max. installation altitude2 000 m
3RU6116-0EB1 — Mechanical
ParameterValue
Width45 mm
Height89 mm
Depth80 mm

Product details

Motor protection relay for the S00 contactor frame

The 3RU6116-0EB1 is a SIRIUS thermal overload relay sized for the S00 contactor frame. It protects a three-phase motor by monitoring current through the main circuit and tripping via a bimetallic thermal element when overload persists.

Mounting and wiring: stand-alone or direct to contactor

The relay supports stand-alone installation in any mounting position. Dimensions are 45 mm wide, 89 mm high, and 80 mm deep — it occupies a single modular DIN-space width. Side clearance to grounded parts must be at least 6 mm. Main circuit and auxiliary circuit connections use screw-type terminals. Auxiliary terminals accept 2× (20…16) or 2× (18…14) AWG. Tightening torque for main contacts is 0.8 to 1.2 N·m.

Environmental limits and compliance documentation

Shock resistance is 8 g for 11 ms per IEC 60068-2-27. Maximum installation altitude is 2,000 m above sea level. Substance prohibitance per RoHS applies from May 1, 2012. Insulation voltage is 690 V at pollution degree 3.

Frequently asked questions

What compliance documentation is available for the 3RU6116-0EB1?

The relay complies with RoHS substance prohibitance effective May 1, 2012. It is designed to IEC standards for thermal overload relays, with insulation voltage rated at 690 V at pollution degree 3.