Fastens directly to a S00-frame contactor via the contactor-mounting method — no bracket or adapter. Mounting position is any orientation, so it fits horizontal, vertical, or flat layouts. Main circuit terminals are screw-type, top and bottom, accepting 2× (0.5...1.5 mm²) solid/stranded or 2× (0.75...2.5 mm²). Auxiliary circuit terminals are also screw-type. Tightening torque for main contacts: 0.8...1.2 N·m. The relay requires 6 mm side spacing to grounded parts. Storage/transport range extends to -55...+80 °C. Installation altitude limit is 2 000 m above sea level. Shock resistance is 8g / 11 ms per IEC 60068-2-27.
Per-pole dissipation is 1.9 W. These numbers matter for enclosure thermal calculations — a sealed cabinet with several relays needs the heat accounted for.