Skip to main content
Siemens 3RU6116-1CB1 — Overload Relays

Siemens 3RU6116-1CB1 SIRIUS Thermal Overload Relay, 1.8-2.5

MPN3RU6116-1CB1

Siemens SIRIUS thermal overload relay, 3RU6116-1CB1, size S00, adjustable 1.8-2.5 A, Class 10 trip, screw terminals, stand-alone installation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RU6116-1CB1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationThermal overload relay
Combinable contactor sizesS00
3RU6116-1CB1 — Protection & Trip
ParameterValue
Overload current setting range1.8 ... 2.5 A
Trip classCLASS 10
Overload release typethermal
3RU6116-1CB1 — Electrical (main circuit)
ParameterValue
Rated operational current2.5 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)5.7 W
Per pole1.9 W
3RU6116-1CB1 — Auxiliary contacts
ParameterValue
Switching current at 24 V2 A
Switching current at 110 V0.22 A
Switching current at 230 V2 A
3RU6116-1CB1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Conductor cross-section: solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range (AWG), main contacts2x (20 ... 16), 2x (20 ... 18), 2x 12
Conductor range (AWG), auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
3RU6116-1CB1 — Environmental
ParameterValue
Operating temperature-40 ... +70 °C
Transport temperature-55 ... +80 °C
Relative humidity, operating0 ... 90 %
Max. installation altitude2 000 m
3RU6116-1CB1 — Mechanical
ParameterValue
Width45 mm
Height89 mm
Depth80 mm

Product details

The Siemens 3RU6116-1CB1 is a SIRIUS thermal overload relay for motor protection, sized S00, with an adjustable current response value of 1.8 to 2.5 A and a Trip Class 10 characteristic. Rated operational current is 2.5 A at 690 V, 50/60 Hz, making it suitable for small motor branches in control panels and motor control centers.

Designed for stand-alone installation — it mounts independently, not directly on a contactor coil, so you need to wire it between the contactor and the motor. Fastening method is stand-alone, and mounting position is any orientation. Width is 45 mm and depth is 80 mm, fitting a standard DIN-rail footprint for size S00 components. Required spacing to grounded parts at the side is 6 mm — factor that into your panel layout. Main circuit connections are screw-type terminals, top and bottom, accepting 2×(0.5…1.5 mm²) solid/stranded or 2×(0.75…2.5 mm²) finely stranded with ferrules. Tightening torque is 0.8…1.2 N·m.

Compliance documentation includes RoHS compliance with substance prohibition date of May 1, 2012, and the relay carries a 6 kV surge voltage resistance rating per IEC 60947.

Frequently asked questions

What are the key ratings for this overload relay?

The adjustable current range is 1.8 to 2.5 A with a Trip Class 10 characteristic. Rated operational current is 2.5 A at 690 V, 50/60 Hz. Power loss at rated current in hot state is 5.7 W typical.

What compliance documentation is available for the 3RU6116-1CB1?

The relay is RoHS compliant with a substance prohibition date of May 1, 2012. Surge voltage resistance is rated at 6 kV, and insulation voltage is 690 V at pollution degree 3.

MPN
3RU6116-1CB1