Skip to main content
Siemens 3RU7116-1EB0 — Overload Relays

Siemens 3RU7116-1EB0 SIRIUS Thermal Overload Relay, 4 A, Cla

MPN3RU7116-1EB0

Siemens SIRIUS thermal overload relay, 3RU7116-1EB0, size S00, 4 A rated operational current, Class 10 trip, contactor-mount, screw terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RU7116-1EB0 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationThermal overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
3RU7116-1EB0 — Protection & Trip
ParameterValue
Overload current setting range2.8 ... 4 A
Trip classCLASS 10
Overload release typethermal
3RU7116-1EB0 — Electrical (main circuit)
ParameterValue
Rated operational current4 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)5.7 W
Per pole1.9 W
3RU7116-1EB0 — Auxiliary contacts
ParameterValue
Switching current at 24 V3 A
Switching current at 230 V2 A
3RU7116-1EB0 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionwith vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Conductor cross-section: solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RU7116-1EB0 — Environmental
ParameterValue
Operating temperature-20 ... +55 °C
Transport temperature-25 ... +70 °C
Relative humidity, operating0 ... 90 %
Max. installation altitude2 000 m
3RU7116-1EB0 — Mechanical
ParameterValue
Width45 mm
Height87 mm
Depth78 mm

Product details

It mounts directly onto a matching contactor — no separate base needed — and protects three-phase motor circuits against overload and phase-loss conditions.

Rated operational current is 4 A at the main circuit, with a maximum operating voltage of 690 V AC/DC at 50/60 Hz. The auxiliary contacts are rated 3 A at 24 V and 2 A at 230 V, and the DC-13 rating for the auxiliary is 1 A at 24 V — enough for PLC-level signal switching. The mounting position allows ±135° rotation and ±45° tilt from vertical, which gives flexibility in tight panels.

This relay is designed for contactor mounting — it clips directly onto the matching S00 contactor (e.g., 3RT2015 or similar), saving a DIN-rail slot. The main circuit connects via screw terminals at top and bottom, accepting 2× (0.5…1.5 mm²) solid/stranded or 2× (0.75…2.5 mm²) with ferrules.

Frequently asked questions

What are the key dimensions?

Depth is 78 mm, width 45 mm, height 87 mm — size S00 frame.

Will it drop into a panel specified around a 3RT1015-1BB42 contactor?

The 3RU7116-1EB0 is size S00 and designed for contactor mounting onto S00 frames. The 3RT1015-1BB42 is also size S00, so the relay clips directly onto it without rewiring the main circuit — same footprint, same terminal arrangement.

What compliance documentation is available?

The relay carries a rated impulse withstand voltage of 6 kV and insulation voltage of 690 V at pollution degree 3, which aligns with IEC 60947-4-1. The evidence does not list UL, CSA, or RoHS certs specifically, but as a standard Siemens SIRIUS catalog item, it typically ships with CE and IEC declarations. Confirm with your order documentation.

MPN