It mounts directly to a matching S00 contactor, forming a compact motor starter assembly for DIN-rail or panel-mount enclosures. Rated operational current is 6.3 A at up to 690 V AC/DC, 50/60 Hz, with a CLASS 10 trip characteristic — meaning it will trip within 10 seconds at 7.2× the current setting, appropriate for standard induction motor starting profiles where the rotor doesn't stall.
The 6.3 A rated operational current sets the maximum continuous motor FLA this relay can protect. For a motor drawing, say, 5.5 A FLA, this relay adjusts down to cover it — the setting range is typically 0.1× to 1.0× of the rated value, so it covers motors from roughly 0.63 A up to 6.3 A. Mounting position allows ±135° rotation and ±45° tilt from vertical, giving flexibility in tight panel layouts. Side spacing to grounded parts must be at least 6 mm to maintain rated insulation.