Skip to main content
Siemens 3RV1011-0AA10-0FJ0-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0AA10-0FJ0-ZX95 SIRIUS Motor Protection CB,

MPN3RV1011-0AA10-0FJ0-ZX95

Siemens SIRIUS, motor protection circuit breaker, 3RV1011-0AA10-0FJ0-ZX95, 0.16 A continuous current, CLASS 10, 100 kA breaking capacity at 400 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-0AA10-0FJ0-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1011-0AA10-0FJ0-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1011-0AA10-0FJ0-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1011-0AA10-0FJ0-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1011-0AA10-0FJ0-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1011-0AA10-0FJ0-ZX95 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting positionany
3RV1011-0AA10-0FJ0-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1011-0AA10-0FJ0-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker, 0.16 A, CLASS 10

The 100 kA breaking capacity holds across 240 V, 400 V, 500 V, and 690 V AC, so it can be placed upstream of a motor starter without worrying about fault-current escalation into the contactor.

Occupies 45 mm width on the rail. Terminals accept solid or stranded conductors: 2× (0.5...1.5 mm²) or 2× (0.75...2.5 mm²) per clamp.

Shock rated at 25g / 11 ms. Mountable in any position. IP20 front protection means it is suitable for enclosed panels, not washdown areas.

Frequently asked questions

Where can I buy 3RV1011-0AA10-0FJ0-ZX95 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the continuous current rating of 3RV1011-0AA10-0FJ0-ZX95?

The continuous current rating is 0.16 A. This is a very low setting, suitable for fractional-horsepower motors or small transformer primaries.

What breaking capacity does this breaker have at 400 V?

It delivers 100 kA breaking capacity at 400 V AC, and the same 100 kA rating holds at 240 V, 500 V, and 690 V AC.

Does 3RV1011-0AA10-0FJ0-ZX95 detect phase failure?

Yes, phase failure detection is included. The breaker will trip if one phase is lost, protecting the motor from single-phasing.

MPN
3RV1011-0AA10-0FJ0-ZX95