Its adjustable overload release spans 0.11 to 0.16 A, and the magnetic short-circuit trip responds at 2.1 A — so it protects a motor drawing 0.16 A at 400 V AC-3 (rated at 0.04 kW) against both sustained overload and bolted faults.
The S00 footprint — 45 mm wide, 90 mm tall, 75 mm deep — leaves room for a contactor of the same S00 frame alongside in a motor starter combo. Clearance requirements: 20 mm above and below, 9 mm to the side, zero forward or backward. IP20 finger-safe front protection means it's suited for enclosed panels where operators reach in for maintenance.