Breaking capacity is 100 kA at 240 V, 400 V, 500 V, and 690 V — that covers most industrial distribution panels up to the main feeder without needing a current-limiting upstream device. Clearance: 20 mm above and below, 9 mm to the side, zero forward or backward.
Mounts on 35 mm standard rail per DIN EN 60715, screw or snap-on. Any mounting position allowed. Terminal screws are M3 for the main contacts, accepting 2x (0.5...1.5 mm²) or 2x (0.75...2.5 mm²) solid or stranded.