Skip to main content
Siemens 3RV1011-0BA20 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0BA20 SIRIUS Motor Protection Circuit Breake

MPN3RV1011-0BA20

Siemens SIRIUS motor protection circuit breaker, 3RV1011-0BA20, 0.2 A continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, spring-loaded terminals, 45 mm width.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-0BA20 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-0BA20 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1011-0BA20 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1011-0BA20 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1011-0BA20 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)

Mechanical

3RV1011-0BA20 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting positionany

Environmental

3RV1011-0BA20 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1011-0BA20 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens SIRIUS 3RV1011-0BA20 is a motor protection circuit breaker sized for a 0.06 kW motor at 400 V AC, with a continuous current rating of 0.2 A and a CLASS 10 trip characteristic. It delivers 100 kA breaking capacity across 240 V through 690 V AC, so it can interrupt high fault currents without upstream coordination concerns in most industrial panels. Phase failure detection is built in, and the main circuit connects via spring-loaded terminals accepting 2x (0.25... 2.5 mm²) solid or 2x (0.25... 1.5 mm²) finely stranded with ferrule.

Mounting and integration

Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 50022, with zero clearance required at the sides or rear. The 45 mm width and 90 mm height fit standard panel layouts; IP20 on the front face means it is protected against finger contact but not washdown — keep it inside an enclosure. Any mounting position is allowed, and the operating range of -20 to +60 °C covers most indoor industrial environments.

Frequently asked questions

Where can I buy 3RV1011-0BA20 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is 3RV1011-0BA20's listed depth?

The depth is 81 mm, which fits standard 35 mm DIN rail enclosures with typical clearance.

What wire sizes does the spring-loaded terminal accept?

The main circuit terminals accept 2x (0.25... 2.5 mm²) solid or 2x (0.25... 1.5 mm²) finely stranded with core end processing. AWG equivalents are 2x (24... 14).

Will 3RV1011-0BA20 drop into a panel specified around 3RV1011-0GA10 without rewiring?

Both share the same 45 mm width, 90 mm height, and DIN rail mounting, so the physical fit is identical. The 0BA20 is rated 0.2 A continuous versus the 0GA10's higher rating — verify the motor FLA matches before swapping; the terminal type and wiring capacity are the same spring-loaded design.

MPN