Mounting and Integration
The 3RV1011-0CA10-ZW95: Mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, in any mounting position. Dimensions are 45 mm wide, 90 mm high, and 75 mm deep. Clearance requirements: 20 mm upwards, 20 mm downwards, 9 mm at the side, 0 mm forwards and backwards. This means it fits standard panel layouts with minimal spacing overhead — a direct drop-in for existing SIRIUS 3RV1 footprints.
Ratings and Protection
Trip Class 10 means the breaker trips within 10 seconds at 7.2× the thermal setting — standard for protecting standard induction motors during locked-rotor conditions. Phase failure detection is built in, which prevents single-phasing damage on a three-phase motor. The 100 kA breaking capacity holds at 240 V, 400 V, 500 V, and 690 V AC, giving solid SCCR headroom for most industrial distribution panels.