Skip to main content
Siemens 3RV1011-0EA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0EA10 SIRIUS Motor Protection Circuit Breake

MPN3RV1011-0EA10
Active

Siemens SIRIUS 3RV1011-0EA10 motor protection circuit breaker, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw and snap-on 35 mm DIN rail mount, phase failure detection, 45 mm wide.

StockContact for availability
Lead timeCall for availability wk
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-0EA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-0EA10 — Electrical
ParameterValue
Rated operational current (Ie)0.4 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1011-0EA10 — Protection & Tripping
ParameterValue
Overload release setting range0.28 ... 0.4 A
Instantaneous short-circuit trip current5.2 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-0EA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV1011-0EA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-0EA10 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV1011-0EA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV1011-0EA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

What it is and what it does

The Siemens 3RV1011-0EA10 is a SIRIUS motor protection circuit breaker designed specifically for motor protection duty, with a Class 10 trip characteristic that clears overloads within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during stall or jam conditions. Rated breaking capacity hits 100 kA at 400 V AC (and at 240 V, 500 V, and 690 V as well), meaning it can safely interrupt a bolted fault up to that level without upstream fuses — useful for high-fault panels where SCCR coordination matters. It includes phase failure detection, so a lost phase on a three-phase motor triggers a trip rather than letting the motor single-phase and overheat.

Panel fit and mounting

Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715 — the same rail as every other SIRIUS 3RV1 breaker, so it drops into an existing panel layout without drilling or adapter plates. Footprint is 45 mm wide × 90 mm high × 75 mm deep, with 20 mm clearance needed above and below, 9 mm to the side, and zero forward or backward clearance required — tight-panel friendly. Main circuit connections use screw-type terminals accepting 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded — standard M3 screws, no special tooling. Mounting position is any orientation; operating temperature range is -20 to +60 °C, storage and transport -50 to +80 °C.

Lifecycle and sourcing

Lifecycle stage is current; no end-of-life notice or last-time-buy date.

Frequently asked questions

Will 3RV1011-0EA10 drop into a panel built for 3RV1011-0GA10?

Yes — same 45 mm width, same 35 mm DIN rail mount, same screw terminal pattern. The 0GA10 variant differs in its rated current range and possibly auxiliary contact configuration, but the mechanical footprint is identical.

MPN
3RV1011-0EA10