The 100 kA breaking capacity at 400 V AC means it can safely interrupt high fault currents on a 400 V line without upstream fuses — a key spec for panel builders sizing the branch circuit.
Trip class and thermal-magnetic curve
Trip Class 10 means the breaker trips within 10 seconds at 7.2× the thermal setting — standard for standard-capability motor starting where the inrush clears before the curve catches it. The thermal element protects against sustained overload; the magnetic element handles short-circuit.