Skip to main content
Siemens 3RV1011-0EA10-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0EA10-ZW96 SIRIUS Motor Protection Circuit B

MPN3RV1011-0EA10-ZW96
Active

Siemens SIRIUS motor protection circuit breaker, 3RV1011-0EA10-ZW96, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting onto 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-0EA10-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-0EA10-ZW96 — Electrical
ParameterValue
Rated operational current (Ie)0.4 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1011-0EA10-ZW96 — Protection & Tripping
ParameterValue
Overload release setting range0.28 ... 0.4 A
Instantaneous short-circuit trip current5.2 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-0EA10-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV1011-0EA10-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-0EA10-ZW96 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV1011-0EA10-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV1011-0EA10-ZW96 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens 3RV1011-0EA10-ZW96 is a SIRIUS motor protection circuit breaker designed for motor protection, with screw-type terminals and phase failure detection. It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, in any orientation. The 100 kA breaking capacity at 400 V AC means it can safely interrupt high fault currents on a 400 V line without upstream fuses — a key spec for panel builders sizing the branch circuit.

Trip class and thermal-magnetic curve

Trip Class 10 means the breaker trips within 10 seconds at 7.2× the thermal setting — standard for standard-capability motor starting where the inrush clears before the curve catches it. The thermal element protects against sustained overload; the magnetic element handles short-circuit. Phase failure detection is built in, so a lost phase on a three-phase motor will trip the breaker rather than letting the motor single-phase and overheat.

Mounting and wiring

The 45 mm width (three module spaces on a DIN rail) and 75 mm depth fit standard distribution panels. Screw terminals accept 2×(0.5…1.5 mm²) solid or stranded, or 2×(0.75…2.5 mm²) — fine for motor branch circuits up to the rated current. Clearance: 20 mm upwards and downwards, 9 mm at the side, 0 mm forwards and backwards. No additional clearance required at 240 V, 400 V, 500 V, or 690 V.

Frequently asked questions

Will 3RV1011-0EA10-ZW96 drop into a panel specified around 3RV1011-0GA10 without rewiring?

Yes — same 45 mm width, same 75 mm depth, same screw-terminal wire range, same DIN-rail mounting. The difference is the thermal-magnetic setting range; check that the ZW96 variant covers your motor FLA.

Where can I buy 3RV1011-0EA10-ZW96?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What is the breaking capacity at 400 V?

100 kA at 400 V AC — sufficient for most industrial motor branch circuits without upstream current-limiting fuses.

MPN
3RV1011-0EA10-ZW96