Trip class is CLASS 10, so it clears a locked-rotor condition within 10 seconds at the rated current — standard for general-purpose motor protection on pumps, fans, and conveyors where the motor can tolerate a brief stall without damage.
The 45 mm width (three module spaces) fits standard panel layouts; depth is 75 mm, height 90 mm. Clearance requirements: 20 mm upward, 20 mm downward, 9 mm at the side — no extra space needed forward or backward. Terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded copper. Screw-type main contacts use M3 screws.