The adjustable overload release is set at 0.28...0.4 A, and the magnetic short-circuit trip responds at 5.2 A. At 400 V it handles a 0.1 kW motor load. The unit includes a factory-fitted transverse auxiliary switch with one normally-open and one normally-closed contact, saving a separate accessory order for status feedback or signaling.
The front is IP20 finger-safe per IEC 60529.