3RV1011-0EA20-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1011-0EA20-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1011-0EA20-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range0.28 ... 0.4 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1011-0EA20-ZX95 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1011-0EA20-ZX95 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)
Conductor range, AWG (main contacts)2x (24 ... 14)
3RV1011-0EA20-ZX95 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1011-0EA20-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1011-0EA20-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

SIRIUS 3RV1011-0EA20-ZX95 — motor protection breaker, 0.4 A, CLASS 10

The Siemens SIRIUS 3RV1011-0EA20-ZX95 is a motor protection circuit breaker designed for a 0.4 A continuous rated current, sized for a 0.09 kW motor at 400 V. Breaking capacity hits 100 kA at 400 V (and at 240 V, 500 V, and 690 V), so it can interrupt a bolted fault up to that level without upstream fuses needing to clear first. That 100 kA SCCR rating covers most industrial panel bus bracing requirements. No ground fault detection on this variant. Spring-loaded terminals on both main and auxiliary circuits accept 2x (0.25 to 2.5 mm²) solid or 2x (0.25 to 1.5 mm²) finely stranded with ferrules. AWG equivalent is 2x (24 to 14). No lug torque to worry about — strip 8 mm, push in, done.

Zero clearance needed at the back or sides, so you can pack it tight on the rail. Rated for any mounting position. Shock rated at 25g / 11 ms — survives the vibration and bump common in panel-mounted gear near conveyors or compressors.

RoHS compliance date is 01.01.2013 — meets the EU RoHS directive. Surge voltage resistance rated at 6000 V, which aligns with IEC 60947-2 overvoltage category III requirements for industrial control panels.

This is a fast-moving critical spare for any panel with 0.4 A motor branches — keep one on the shelf if you've got a line using this amp rating.

Frequently asked questions

Where can I buy 3RV1011-0EA20-ZX95 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing.

What is the closest functional alternative to 3RV1011-0EA20-ZX95?

The 3RV1011-0GA10 and 3RV1011-0HA10 are peer MPNs in the same SIRIUS 3RV1 family. The -0GA10 uses screw terminals instead of spring-loaded; the -0HA10 has a different current rating. Both share the same 45 mm width and CLASS 10 trip characteristic, so they drop into the same DIN-rail slot without panel rework, but verify the current setting matches your motor FLA.

What compliance documentation does this brand provide for 3RV1011-0EA20-ZX95?

RoHS compliance is confirmed with a substance prohibition date of 01.01.2013. The part carries a surge voltage resistance rating of 6000 V, consistent with IEC 60947-2. Standard Siemens documentation includes a CE declaration and manufacturer's declaration of conformity.

MPN
3RV1011-0EA20-ZX95