The 100 kA breaking capacity at 400 V (and at 240 V, 500 V, and 690 V) means this device can safely interrupt fault currents up to that level without cascading upstream, which is the figure that governs panel SCCR coordination.
Screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²). The M3 terminal screws for the main contacts are sized for control wiring. Clearance requirements: 20 mm upwards and downwards, 9 mm at the sides, zero forwards and backwards — tight panel packing is possible.