It is rated CLASS 10 for thermal overload protection, with an A-release (overload) set at 0.35 to 0.5 A and an N-release (short-circuit) at 6.5 A. The unit includes a factory-fitted transverse auxiliary switch with one normally-open and one normally-closed contact, and uses screw terminals for wiring.
The 0.35–0.5 A overload range fits small motors (roughly 0.09–0.12 kW at 400 V three-phase). The 6.5 A magnetic short-circuit release is fixed and non-adjustable; it must coordinate with the upstream feeder breaker.