Skip to main content
Siemens 3RV1011-0GA10-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0GA10-ZW96 SIRIUS Motor Protection Circuit B

MPN3RV1011-0GA10-ZW96
Active

Siemens SIRIUS motor protection circuit breaker, 3RV1011-0GA10-ZW96, CLASS 10, 100 kA breaking capacity at 400 V, screw and snap-on 35 mm DIN rail, 45 x 90 x 75 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-0GA10-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV1011-0GA10-ZW96 — Electrical
ParameterValue
Rated operational current (Ie)0.63 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1011-0GA10-ZW96 — Protection & Tripping
ParameterValue
Overload release setting range0.45 ... 0.63 A
Instantaneous short-circuit trip current8.2 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1011-0GA10-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV1011-0GA10-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1011-0GA10-ZW96 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV1011-0GA10-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV1011-0GA10-ZW96 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Rated for breaking capacities up to 100 kA at 240 V, 400 V, 500 V, and 690 V AC — meaning it can safely interrupt very high fault currents without upstream fuses at those voltages, simplifying panel coordination. Mounts via screw and snap-on onto a 35 mm DIN rail per DIN EN 60715, and accepts screw-type terminals for the main circuit with conductor cross-sections up to 2x 2.5 mm² solid or stranded. Dimensions are 45 mm wide, 90 mm high, 75 mm deep, with clearance requirements: 20 mm upward, 20 mm downward, 9 mm at the side, and no clearance needed forward or backward.

Integration Notes

The 45 mm width fits standard DIN-rail spacing; the screw-type terminals accept 2x (0.5…1.5 mm²) or 2x (0.75…2.5 mm²) solid or stranded conductors, M3 for main contacts. Mounting position any. Rated voltage range 20…690 V; at 230 V the motor power rating is 0.1 kW. Maximum switching frequency at AC-3 and AC-3e is 15 operations per hour.

Frequently asked questions

Will 3RV1011-0GA10-ZW96 drop into a panel specified around 3RV1011-0GA10?

Yes — the base part 3RV1011-0GA10 shares the same physical footprint and mounting (45 mm wide, screw and snap-on 35 mm DIN rail), so it is a drop-in replacement.

MPN
3RV1011-0GA10-ZW96