Skip to main content
Siemens 3RV1011-0HA10-0FJ0-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens SIRIUS 3RV1011-0HA10-0FJ0-ZX95 Motor Protection Circ

MPN3RV1011-0HA10-0FJ0-ZX95

Siemens SIRIUS, motor protection circuit breaker, 3RV1011-0HA10-0FJ0-ZX95, rated continuous current 0.8 A, CLASS 10 trip, breaking capacity 100 kA at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-0HA10-0FJ0-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-0HA10-0FJ0-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1011-0HA10-0FJ0-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1011-0HA10-0FJ0-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1011-0HA10-0FJ0-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-0HA10-0FJ0-ZX95 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting positionany

Environmental

3RV1011-0HA10-0FJ0-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1011-0HA10-0FJ0-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

What it is — and what the ratings mean for your panel

The Siemens SIRIUS 3RV1011-0HA10-0FJ0-ZX95 is a motor protection circuit breaker designed for motor loads up to 0.18 kW at 400 V. The 0.8 A continuous rated current sets the maximum steady-state load it can carry through the main contacts without tripping — size it so the motor's full-load amps sit below this figure. The CLASS 10 trip characteristic means it will interrupt on overload within 10 seconds at 7.2× rated current, which is the standard protection curve for standard induction motors starting against light loads (pumps, fans, compressors). That 100 kA breaking capacity at 400 V AC means it can safely clear a short-circuit fault up to 100,000 A without welding contacts or rupturing — critical for high-fault-current panels downstream of a large transformer. Mounts on 35 mm DIN rail per DIN EN 50022 via screw and snap-on — the same footprint as the standard SIRIUS 3RV1 family, so it drops into existing panels without drilling. The IP20 finger-safe front cover and 45 mm width (3 modules wide) fit standard enclosure cutouts.

Integration details — terminal capacity and clearances

Screw-type terminals on the main circuit accept solid or stranded conductors: 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²), or AWG 18 to 14. No auxiliary contacts are fitted (0 for auxiliary contacts), but the unit supports a side-mounted auxiliary switch block if needed. Zero clearance required at the rear (0 mm backwards) and at the sides (0 mm at the side) — it can be butted directly against adjacent devices on the rail. Operating temperature range -20 to +60 °C; storage and transport range -50 to +80 °C.

Frequently asked questions

What is the breaking capacity of this motor protection circuit breaker?

100 kA at 240 V, 400 V, 500 V, and 690 V AC — the same high interrupting rating across the voltage range, so coordination with upstream breakers is straightforward.

Will 3RV1011-0HA10-0FJ0-ZX95 drop into a panel that was specified around 3RV1011-0HA10 without rewiring?

Yes — same 45 mm width, same screw and snap-on DIN rail mount, same terminal capacity (0.5 to 2.5 mm² solid/stranded). The -0FJ0-ZX95 suffix indicates a special variant, but the mechanical footprint and wiring interface are identical to the standard 3RV1011-0HA10.

Where can I buy 3RV1011-0HA10-0FJ0-ZX95 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

MPN
3RV1011-0HA10-0FJ0-ZX95