Siemens SIRIUS 3RV1011-0HA10-ZW96, motor protection circuit breaker, Class 10, screw-type terminals, 45 mm width, 90 mm height, 75 mm depth, DIN rail snap-on.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-0HA10-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-0HA10-ZW96 — Electrical
ParameterValue
Rated operational current (Ie)0.8 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1011-0HA10-ZW96 — Protection & Tripping
ParameterValue
Overload release setting range0.55 ... 0.8 A
Instantaneous short-circuit trip current10 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-0HA10-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV1011-0HA10-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-0HA10-ZW96 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV1011-0HA10-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV1011-0HA10-ZW96 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens SIRIUS 3RV1011-0HA10-ZW96 is a motor protection circuit breaker designed for Class 10 trip characteristics, meaning it will trip within 10 seconds at 7.2x the thermal setting. This is the standard protection for standard induction motors starting under load — pumps, conveyors, compressors. It includes phase failure detection, which opens the circuit if one phase drops out, preventing single-phasing damage.

Mounting and Integration

Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715. Dimensions are 45 mm wide, 90 mm high, 75 mm deep. Requires 20 mm clearance above and below, 9 mm at the sides, zero forward or backward clearance. Can be mounted in any position. The screw-type terminals accept 2x (0.5...1.5 mm²) or 2x (0.75...2.5 mm²) solid or stranded wire, terminated with M3 screws on the main contacts.

Ratings and Application

Rated operating voltage range is 20...690 V. Breaking capacity is 100 kA at 240 V, 400 V, 500 V, and 690 V AC. At 230 V, the motor power rating is 0.1 kW. The maximum switching frequency at AC-3 duty is 15 operations per hour. For short-circuit protection at 500 V and 690 V, the required backup fuse is gL/gG 6 A. Operating temperature range is -20 to +60 °C; storage and transport range is -50 to +80 °C.

Frequently asked questions

Where can I buy 3RV1011-0HA10-ZW96 and how is it quoted?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the depth of 3RV1011-0HA10-ZW96?

The depth is 75 mm. The overall dimensions are 45 mm wide, 90 mm high, and 75 mm deep.

What trip class does this circuit breaker have?

It is Class 10, meaning it will trip within 10 seconds at 7.2 times the thermal setting. This is standard for motor starting under load.